33-35 kV Outdoor Current Transformer
Product Parameters:
MODEL:33-40.5 kV Outdoor Current Transformer
· Outdoor epoxy resin current transformer
· Single phase
· Rated voltage: 33kV, 35kV, 36kV, 40.5kV
· Metering class for CT: 0.2S, 0.2, 0.3, 0.5, 0.5S, 0.6
· Standard: IEC, ANSI, GB
· Type name: LZZW-33, LZZBW-33, LZZW-35, LZZW-36
General
This outdoor dry type current transformer is used in 33kV, 35kV, 36kV and 40.5kV power system, for measuring and protection.
It has been used in outdoor pole mounted and transmission line.
The current transformer is made from high quality ultraviolet-proof epoxy resin, amorphous alloy core for metering and high quality CRGO core for protection, primary and secondary use pure electrolytic copper, both winding and core have shielding processing.
Standard
All UNISUN Electric instrument transformers are in conformity with IEC standards, and recommendations IEC 61869. Transformers in conformity with specific country standards can also be supplied. (IEEE C57.13, NBR6855).
Specification data she
| Rated primary current(A) | Accuracy classes combination | Accuracy class and output (VA) | Short-time thermal current(kA/1s) | Rated dynamic current(kA) | ||||||
| 0.2s | 0.2 | 0.5s | 0.5 | 10p10 | 10p15 | 10p20 | ||||
| 5 | 0.2S/10P10 0.2S/10P15 | 10 | 10 | 10 | 10 | 15 | 15 | 15 | 0.5 | 12.5 |
| 10 | 1 | 2.5 | ||||||||
| 15 | 1.5 | 3.75 | ||||||||
| 20 | 2 | 5 | ||||||||
| 25 | 2.5 | 6.25 | ||||||||
| 30 | 3 | 7.5 | ||||||||
| 40 | 4 | 10 | ||||||||
| 50 | 5 | 12.5 | ||||||||
| 75 | 7.5 | 18.75 | ||||||||
| 100 | 10 | 10 | 10 | 10 | 15 | 15 | 15 | 10 | 25 | |
| 150 | 15 | 37.5 | ||||||||
| 200 | 20 | 50 | ||||||||
| 300 | 30 | 75 | ||||||||
| 400 | 40 | 100 | ||||||||
| 500 | 50 | 75 | ||||||||
| 600 | 15 | 15 | 15 | 15 | 20 | 20 | 20 | 60 | 150 | |
| 800 | 15 | 15 | 15 | 15 | 20 | 20 | 20 | 80 | 200 | |
| 1000 | 15 | 20 | 15 | 30 | 30 | 30 | 20 | 80 | 200 | |
| 1200 | 80 | 200 | ||||||||
| 1500 | 80 | 200 | ||||||||
| 2000 | 80 | 200 | ||||||||
- Products can be customized by customer requirements, above data is standard data, customized data please contact us.
- Products can be customized by customer requirements, above dimension may change, correct dimension please contact us.
Why Buy From Us
- Certified to international quality standards; core components meet the standards.
- Easy payment and affordable prices.
- Easy to use and excellent service
Primary Winding:
A high-electrolytic copper primary winding is used, and a silver-base welding material is used at the welding place. Semiconductor shielded paper is wrapped around it to ensure that the partial discharge testing data is qualified.
Secondary Winding
The large-capacity secondary winding is automatically wound with high-insulation, high-purity enameled wire to ensure a wide capacity output under standard accuracy.